| [Home] | |
| |
|
By R. V. Simha
Air Conditioning Consultant
Airtron, Bangalore
R. V. Simha is a graduate engineer in both mechanical and electrical engineering, with over 40 years of experience in HVAC. He has been a pracitising consultant for the last 25 years. He is an active member of ISHRAE and ASHRAE South India chapter.
Cold air distribution systems supply air at 40 45°F instead of the conventional 55°F to cut down air flow rate, air handling unit size and duct dimensions. Similarly using high-rise chilled water coils, water flow rate, pump capacity and pipe sizes can be cut down. Thus saving operating costs. Why not use more such systems in new HVAC designs for commercial and office buildings?
In a conventional air conditioning system (CAC), the supply air temperature is about 55°F(13°C) for comfort air conditioning. This gives a temperature differential of 20°F (11°C) between room 75°F (24°C) and supply air. In a cold air system (CAS), the supply air temperature will be at about 45°F (7°C) for a room temperature of 78°F(25.6°C) which, as will be seen later, is acceptable in CAS yielding a temperature differential of 33 38°F (0.5 3°C). Accordingly, in a CAS, the dehumidified air flow rate will be only about 50-60% of the value in CAC for the numbers cited above. Although there is a great deal more to CAS, this is its trademark.
Figure 1 shows the summer schematic for the CAS. The inside design conditions are 78°F db and 35% rh. The return air is divided into two streams the first is the quantum of air that is equal to the outside air-flow rate and which is exhausted through a heat wheel. The second the remainder of the return air is drawn back directly by the AHU.
The incoming outside air is cooled and dehumidified by the first stream of the return air, which as noted earlier, is exhausted through the heat wheel. The AHU therefore handles a mixture of outside air, that emerges from the heat wheel duly cooled and dehumidified and the second stream of return air that arrives directly from the room. It is this mixture that passes through the cooling coil of the AHU. Figure 2 shows the cooling process on a psychrometric chart.
Brine is supplied to the cooling coil at 35°F (in lieu of 44 to 45°F used in a CAC). Thus, the air that leaves the coil, can be at 40 45°F.
The selected room relative humidity is 35%. This low rh even at 78°F db, as can be seen from the ASHRAE Comfort Chart (Figure 3) is close to the comfort level obtained at 74°F db and 55% rh. In other words full advantage is taken of the lower relative humidity that is readily achieved in the CAS, to elevate the room db to 78°F. This, in turn, increases the temperature differential between supply air and room correspondingly that is to say, by about 4°F. The resulting benefit will be a further reduction in the dehumidified air flow rate.
It is best however to study the CAS in relation to the conventional systems, using a worked example.
Consider the air conditioning requirements of an office area of 22,500 ft2. Other relevant design data is shown below:
[top]
Based on this data, three cases have been worked out and analyzed in this article:
For CAC 1, the air conditioning load estimates, including transmission and solar, have been made using standard procedures essentially, the ADP method exemplified in the Carrier System Design Manual.
For CAC 2 and CAS, the modified procedure is outlined below :
Calculations have been made for the intermediate season also in addition to
Summer and Monsoon Seasons. The following months constitute the 3 seasons :
Summer : March, April & May
Monsoon : June, July, August, September and October
Intermediate Season : November, December, January and February
The inside design conditions used for the intermediate season i.e., 91°F-db and 70°F-wb have been arrived at on the basis of IMD Data (Climatological Tables of Observatories in India, 1951 - 1980 Fifth Edition 1999).
The highlights of the results of the study are shown in Tables 1, 2, 3 and 4.
| Table 1 : Study of TR & CFM Requirements of CAC-1, CAC2 & CAS | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|
| Sl. No. | Description | CAC -1 | CAC-2 | CAS | ||||||
| Sum. |
Mon. |
Int. |
Sum. |
Mon. |
Int.* |
Sum. |
Mon. |
Int. |
||
| 1 | TR |
118 | 88 | 82 | 89 |
63 |
84 |
77 |
55 |
66 |
| 2 | ADP | 55 | 54 | 55.5 | 55 | 54 | 54 | |||
| 3 | Indicated Summer cfm | 42359 | 42360 | |||||||
| 4 | Adjusted Summer cfm | 42359 | 42360 | 19875 | ||||||
| 5 | Monsoon cfm | 22694 | 22700 | 12000 | ||||||
| 6 | Supply Air Temperature | 56 | 64 | 56.5 | 56 | 64 | 55 | 45 | 45 | |
| Table 2 : Power Requirements | ||||||
|---|---|---|---|---|---|---|
| Sl. No. | Description | CAC | CAS | Remarks | ||
| RTAB - 108 W/o HW |
CGA 600 W/HW |
CGA 600 W/HW |
CAC - 1 | CAC - 2 | ||
| 1 | Chiller kW |
165 |
113 |
108 |
Higher by 50% |
Higher by 30% |
| 2 | Chilled water / Brine Pumps kW |
11 | 7.4 | 4.4 | Higher by 250% | Higher by 250% |
| 3 | AHU Fan kW | 22 | 22 | 15 | Higher by 50% | Higher by 50% |
| 4 | Heat Wheel Exhaust Fan kW | | 3 | 2.2 | _ | _ |
| 5 | Reheat kW | See Note * | 25 | 25 | See Note * | See Note * |
| 198 | 170.4 | 154.6 | highby 40% | highby 20% | ||
| Note : * Reheat for CAC has not been shown since it is not usually provided | ||||||
[top]
| Table 3 : Chiller Selection | |||||
|---|---|---|---|---|---|
| Sl. No. | Description | CAC | CAS | ||
| RTAB 108 W/o HRC |
CGA 600 W/HRC |
CGA 600 W/HRC |
|||
| 1 | Total Capacity required |
TR kW |
118 420 |
89 315 |
78 275.6 |
| 2 | No. of Chillers | 2 | 2 | 2 | |
| 3 | Capacity required per Chiller | TR kW |
59 210 |
44.5 157.0 |
39 137.8 |
| 4 | Capacity of Selected Chiller | TR kW |
60 212 |
43.5 154 |
37.4 132.2 |
| 5 | Flow rate | l/s gpm |
10.1 161.6 |
7.35 117.6 |
3.65 58.4 |
| 6 | Compressor Type | Screw | Scroll | Scroll | |
| 7 | Power input at Design Conditions | kW | 82.5 | 56.5 | 54 |
| 8 | KW / TR | 1.4 | 1.3 | 1.4 | |
| 9 | Total Power | kW | 165 | 113 | 108 |
| 10 | Operating weight of each machines | kgs | 2410 | 1270 | 1270 |
| 11 | Refrigerant Charge | kgs | 56 | 28 | 28 |
| 12 | L x W x H mtrs | 3.1 x 2.1 x 2.1 | 2.3 x 1.9 x 1.6 | 2.3 x 1.9 x 1.6 | |

Click to view the clear picture
[top]
The following features of the CAS may be noted straight away:

Click to view the clear picture

[top]
| Table 4 : Comparative Study of Costing for CAC 1, CAC 2 & CAS | ||||
|---|---|---|---|---|
| Sl. No. | Description |
CAC 1 Amount - Rs. |
CAC 2 Amount - Rs. |
CAS Amount - Rs. |
| 1 | Trane Air Cooled Brine Chilling Machine | 2875000 | ||
| 1 | Trane Air Cooled Water Chilling Machine | 4110000 | 2875000 | |
| 2 | Chilled Brine Pumpsets | 66000 | ||
| 2 | Chilled water Pumpsets | 140000 | 100000 | |
| 3 | Double skin Composite Air Handling Unit | 800000 | 900000 | 700000 |
| 4 | Heat Wheel | 600000 | 600000 | |
| 5 | Sheet metal work | 860000 | 860000 | 828100 |
| 6 | Thermal insulation | 400000 | 400000 | 200000 |
| 7 | Acoustic Insulation | 45500 | 45500 | 28000 |
| 8 | Chilled Brine Piping | 136600 | ||
| 9 | First Charge of Ethylene Glycol | 30000 | ||
| 10 | Chilled Water Piping | 215300 | 211000 | |
| 11 | Hot Water Piping | 144100 | ||
| 12 | Controls | 328500 | 299600 | 280400 |
| 13 | Electrical Work | 328500 | 299600 | 280400 |
| TOTAL | 7227800 | 6590700 | 6168600 | |

CAS Benefits & Advantages The benefits and advantages of CAS can now be listed :
| First Cost (in Rs. Lakhs) |
Energy Cost (in Rs. Lakhs) |
|||
| Alt 1 | Alt 2 | Alt 1 | Alt 2 | |
| CAC |
73 | 66 | 18 | 15 |
| CAS | 62 | | 12.5 | |
[top]
The above costs include chillers, pumpsets, AHUs, sheet metal work, diffusers, fire dampers, volume control dampers, thermal insulation (50 mm EPS or equivalent for all ducting), acoustic lining, chilled water / brine piping, controls and electrical work; also, import duty has been calculated at 55% for chillers and special diffusers (for CAS only).
Heat wheel, VFD for AHU fan motors, hot water pumpsets, hot water coil and hot water piping have also been included for CAS.
The estimate for CAC 2 also includes a heat wheel.
Quantities for sheet metal work with diffusers and other accessories, thermal insulation, acoustic lining etc., have been taken from schematic layouts that were prepared for this study.
A comparative study of costing has been furnished in Table 4. It will be seen that while CAS is about 17% less expensive than CAC 1, it is about 7% less, when compared with CAC 2. Even if, CAC 2 is considered as the alternative to compare with, it is clear that first cost and also energy cost (shown above) is not a constraint in decision-making on the choice of CAS.
Although, the above study has been made for a warm humid coastal climate typified by Mumbai, the CAS has been applied (abroad) for hot dry areas also with appropriate changes in detailed design.
CAS is often regarded as something, which should necessarily go with TSS in order to be viable and attractive. It will be seen however, from the foregoing, that it is an attractive alternative to CAC even when there is no TSS to prop it. Apart from technical considerations, it is competitive in price and energy consumption is lower. It is therefore attractive and viable on its own.
The same remark applies to TSS also i.e., it is viable and attractive on its own. When the two are combined, additional benefits will accrue. Where 45°F water would have been used, TSS produces 35°F (1.7°C) Ethylene Glycol. This can be provided directly to a CAS instead of inserting an interface, like a plate heat exchanger, to raise it to 45°F to suit CAC. If this is done, the cost of producing brine can be equitably debited to TSS and CAS, making each system, in combination with each other, more viable.
When the beneficial effect of TSS in reducing the installed plant capacity is taken into account, the capacity of CAS is further reduced to half i.e. plant capacity will be only about 40 ton as compared to 118 ton for CAC 1 and 88 ton for CAC 2. Inevitably, this will translate to further reductions in first cost and energy cost.
CAS Plants have been gaining in popularity over the past decade in the US and other advanced countries. The earliest TSS installations in this country are about a dozen years old and there are over 30 TSS installations at the present time, including the largest one the Tidal Park installation at Chennai, which went into stream recently. However, to this writers knowledge, CAS has not been provided for any project so far either with TSS or on its own.
A partial list of CAS installations is given below :
With todays emphasis on energy conservation and indoor air quality, there is a clear case for considering CAS, preferably with TSS, for all commercial buildings and office buildings.
CAS benefits and advantages come at no extra cost.
[top]